Title: Genomic characterization and environmental persistence of Legionella pneumophila serogroup 1 in hospital water distribution systems

Names of Authors: Lukas Schneider¹*, Amina Diallo², Rohan Chatterjee³

Abstract: Legionella pneumophila is an opportunistic waterborne bacterium responsible for severe healthcare-associated pneumonia following inhalation of contaminated aerosols. We assessed bacterial colonization levels, sequence-based types, and thermal disinfection efficacy across hospital plumbing networks. Hot water and biofilm swabs from 180 hospital outlets alongside respiratory specimens from 45 nosocomial pneumonia patients were analyzed via culture and quantitative polymerase chain reaction. Legionella pneumophila serogroup 1 sequence type 1 was isolated from 19.4 percent of distal water outlets and matched three clinical cases. Maintaining hot water circulation above 60 degrees Celsius curtails nosocomial Legionnaires disease.

Keywords: Legionella pneumophila, Legionnaires disease, Hospital water systems, Nosocomial pneumonia, Environmental surveillance

Citation: Schneider L, Diallo A, Chatterjee R (2026). Genomic characterization and environmental persistence of Legionella pneumophila serogroup 1 in hospital water distribution systems. African Journal of Infectious Diseases Research, 13(11): 892–899. DOI: 10.46882/AJIDR/149029